式样
| Model | FCP60024WJP | ||
| Cooling method | Thermoelectric device (Thrmo-module) | ||
| Radiating method | Forced water cooling | ||
| Control method | Cooling/Heatng automatic shift PID control | ||
| Circulating Fluid System | Ambient temperature/humidity | 10~35℃, 35~80%RH | |
| Circulating fluid | DI Water | ||
| Operating temperature range | 10.0~60.0℃ | ||
| Cooling capacity | 600W (25℃) ※1 | ||
| Heating capacity | 900W (25℃) ※1 | ||
| Temperature stability | ±0.05℃ ※2 | ||
| Pump | Magnetic drive pump 19L/min, 20m lift | ||
| Tank capacity | Approx. 3.0L | ||
| Port size | IN/OUT | Rc3/8 | |
| Drain | Rc3/8 (with plug) | ||
| Wetted parts material | Stainless steel 304, EPDM, PE, ABS | ||
| Facility water system | Temperature range | 10-35℃ | |
| Pressure range | ≦1MPa | ||
| Required flow rate | 7-15L/min | ||
| Port size | S-IN/S-OUT Rc3/8 | ||
| Watted parts material | Aluminum, Stainless steel 304, EPDM, PE | ||
| Electrical System | Power supply | Single-phase 100 to 240VAC±10%, 50/60Hz | |
| Overcurrent protector | 13.5A | ||
| Current consumption | 7.5A (100V)~3.2A (240V) | ||
| Communications | I/O, ETH, RS232, RS485 | ||
| Weight | Approx21.5kg | ||
| Accessories | Power cable | ||
| Safety standards | EN60204-1 CE marking | ||
※ 1 Ambient temperature 25℃,Facility water temperature 25℃,Set temperature 25℃,Circulating 7L/min
※ 2 Value under stable load without turbulence